V distortion : <1.0%
Input V : 380V
Q factor : Q≥30(f=45Hz)
Output wave : Since wave
F range : 30Hz~300Hz
System accuracy : 1.5%
This series devices are designed for AC withstand voltage test of substation primary equipment under 550KV or below, mainly composed of variable-frequency power supply, exciting transformer, reactor and capacitive Voltage divider
Features:
1. rated voltage:
     27kV--- meets AC withstand voltage test of 10kV cable
working frequency 30-300Hz
                 Test voltage is not more than 22kV, test time is 5min;
     54kV--- meets AC withstand voltage test of 35kV cable
Working frequency 30-300Hz
Test voltage is not more than 52kV, the test time is 60min;
81kV--- meets AC withstand voltage test of 10kV cable
working frequency 30-300Hz
                 Test voltage is not more than 22kV, test time is 5min;
     54kV--- meets AC withstand voltage test of 10kV substation 
Working frequency 30-300Hz
Test voltage is not more than 28kV, test time is 1 min;
108kV--- meets AC withstand voltage test of 35kV sbustation
Working frequency 30-300Hz
Test voltage is not more than 100kV test time is 1 min;
2. output voltage waveform distortion rate: <1.0%
 3. allow continuous working hours: one time working for 60 minutes under rated conditions;
 4. Quality factor of the device: Q > 30 (f=45Hz)
 5. device output waveform: sine wave
 6. input power supply: three phase 380V
 7. frequency regulation range: 30Hz ~ 300Hz
 8. system measurement precision: 1.5%
 9. over voltage, over current, zero start and other protection functions.

COMPOSITION
1. Frequency conversion power supply
 (1) rated power: 7 kW
 (2) Input voltage: three phase 380V 50Hz
 (3) output voltage: 0 ~ 400V adjustable
 (4) Output voltage frequency: 30 ~ 300Hz
 (5) 0.1Hz regulation step
 (6) Frequency instability is less than 0.02%
 (7) Output current: 0 ~ 18.75A
 2.  High voltage reactor (4 units)
 (1) rated working voltage: 27kV
 (2) rated working current: 1.25A
 (3) rated inductance: 100H
 (4) Continuous working time: 60min
 (5) Temperature rise: less than 65ºc
 (6) Working frequency: 30~300Hz
 3.  excitation transformer
 (1) rated capacity: 7.5kVA
 (2) input voltage: 400V
 (3) output voltage: 1.5/3/6kV
 (4) output current: 5/2.5/1.25A
 4. capacitance divider (1 units)
 (1) self capacitance: 800pF
 (2) rated voltage: 110kV
 (3) working frequency: 30 ~ 300Hz
 (4) uncertainty: 1.5%
 (5) Rated voltage: 110kV/800pF
 5. test line (1 sets)
|  			 Configuration Test object  |  			 			 Reactor 4 sections 33.75kVA/27kV  |  			Excitation transformer output terminal | Test voltage(kV) | 
|  			 10kV/300mm²/3km  |  			4 sections in series | 1.5kV | ≤22kV | 
|  			 35kV/300mm²Cable 1km  |  			Two in series two in Parallel | 3kV | ≤52kV | 
| 35kV/100MW Power Transformer | three in series | 6kV | ≤68kV | 
| 10kV substation | two in series | 1.5KV | ≤28kV | 
| 35kV substation | four in series | 6kV | ≤100kV | 

| 
                                             | 
                